KWIKSENSE DIGITAL GAS TRANSMITTER

KwikSense series digital gas transmitter is a field mountable device suitable for the detection and continuous monitoring of hazardous gases at industrial locations. It provides an RS-485 MODBUS-RTU digital output signal that can be connected to any suitable control system viz. Uniphos controller, DCS, PLC, etc. It also provides an industry standard 4-20 mA analog output. The KwikSense is available for a large number of toxic and flammable gases viz. PH3, CO, H2S, SO2, Cl2, NH3, HCN, HCl, NO2, CH4 (%LEL), etc.
Relays Digital Or Analog O/P Brochure
R
R=0 (No relay)
R=1 (With Relay
X
A: Analog 4-20 mA O/P
M: MODBUS & 4-20 mA

SMR = Standard Measuring Range | RES = Resolution
EC = Electro Chemical | NDIR = Non Dispersive Infra Red | PID= Photo Ionization Detection

Gas Code Gas Name Range Res Sensor Type
010A Oxygen 0 – 25% V/V 0.1% V/V EC
015A Ozone 0 – 1 PPM 0.01 PPM EC
020A Carbon Monoxide 0 – 1000 PPM 1 PPM EC
021A Carbon Disulfide 0 – 100 PPM 1 PPM EC
022A Vinyl Chloro Monomer 0 – 100 PPM* 1 PPM EC
023A Styrene 0 – 100 PPM* 1 PPM EC
024A Acrylonitrile 0 – 100 PPM* 1 PPM EC
025A Carbon Dioxide 0 – 5% V/V 0.01% V/V NDIR
025B Carbon Dioxide 0 – 100% V/V 1% V/V NDIR
030A Hydrogen Sulphide 0 – 100 PPM 1 PPM EC
035A Mercaptan 0 – 20 PPM 0.1 PPM EC
040A Sulphur Dioxide 0 – 20 PPM 0.1 PPM EC
050A Phosphine 0 – 10 PPM 0.01 PPM EC
055A Phosgene 0 – 1 PPM 0.01 PPM EC
060A Chlorine 0 – 20 PPM 0.1 PPM EC
061A Bromine 0 – 20 PPM 0.1 PPM EC
070A Hydrogen Chloride 0 – 20 PPM 0.1 PPM EC
071A PCL3 0 – 10 PPM* 1 PPM EC
072A Hydrogen Fluoride 0 – 10 PPM 0.1 PPM EC
073A POCL3 0 – 20 PPM* 1 PPM EC
075A Hydrogen Cyanide 0 – 100 PPM 1 PPM EC
081A Nitrogen Dioxide 0 – 20 PPM 0.1 PPM EC
082A Ammonia 0 – 100 PPM 1 PPM EC
082B Ammonia 0 – 1000 PPM 1 PPM EC
090A Hydrogen 0 – 1000 PPM 1 PPM EC
090B Hydrogen 0 – 100% LEL 1% LEL EC
090C Hydrogen 0 – 100% LEL 1% LEL Pellister
098A Formaldehyde 0 – 10 PPM* 1 PPM EC
099A HC (Methane) 0 – 100% LEL 1% LEL Pellister
099B LPG 0 – 100% LEL 1% LEL Pellister
099C Acetylene 0 – 100% LEL 1% LEL Pellister
099D Butanol 0 – 100% LEL 1% LEL Pellister
099E Methane 0 – 100% LEL 1% LEL NDIR
099F Methane 0 – 100% V/V 1% V/V NDIR
099G HC (Methane) 500 – 10000 PPM* 10 PPM Solid State
099H Hydro Carbon 50 – 1000 PPM * 1 PPM Solid State
100A VOC (isobutylene) 0 – 1000 PPM 1 PPM PID
100B VOC (isobutylene) 0 – 4000 PPM 1 PPM PID

Note : Please contact us for any other special gas requirements other than that specified in the table.

* Please consult factory for further information

Plug & Play Smart Sensor Technology
8×2 backlit alphanumeric LCD display
Non-intrusive calibration using magnetic wand
Tricolor LED for alarm indications
Fully configurable on-board potential free relay contact
Industry standard 4-20mA analog signal output (soft tunable)
3x inbuilt 3 potential free relay contacts (optional)
Input (24V) voltage monitoring and its status prompting on display
Cable fault detection and 4-20mA output signal disable
Inbuilt ambient temperature sensor
User settable alarm set-points
Provision to mute relay output
Self testing of alarm LEDs and relays
Indication for no sensor, over-range, baseline drift
Digital communication by RS 485
CIMFR/ PESO/ ATEX certified to Exd IIC T6, IP66
SIL certified
MED (Coming Soon!)